ATEXshop.de Logo

USB Intrinsic Safety Barrier

Product no.: PF-SK-PC-D2-UU1-10-HS
MPN: SK-PC-D2-UU1-10-HS
ATEX Zonefor zone: 2 (3G)Certified for gas zone 2
ATEX temperature class: T1> 450 °C, T2> 300 bis ≤ 450 °C, T3> 200 bis ≤ 300 °C, T4> 135 bis ≤ 200 °C, T6> 100 bis ≤ 135 °C, T6> 85 bis ≤ 100 °C
ATEX device group
Group I: Equipment for use in mining / overground / underground operations
Group II: Equipment for use in potentially explosive gas atmospheres
Group III: Equipment for use in potentially explosive dust atmospheres
:
IIAPropane> 180μJ, IIBEthylene 60 ... 180μJ, IICHydrogen <60μJ

File

232,31 EUR
16 % VAT plus. excl. Shipping costs


The SK-PC-D2-UU1-10-HS is an open-type USB barrier that provides two
USB channel connections. The barrier is intended for installation into an
ATEX/IECEx certified, tool-removable, IP54 minimum enclosure and is
suitable for installation in Zone 2, Group IIC hazardous locations. The
barrier provides "ic" energy-limited field wiring to Zone 2, Group IIC and
Zone 22, Group IIIB hazardous locations.
For each of the two USB channels, the barrier provides four lines to the "ic"
intrinsically safe apparatus: The power lines (V+, GND) and the data lines
(TxD+, RxD-)
The SK-PC-D2-UU1-10-HS may be mounted in Class I, Div. 2, A, B, C, D
and Zone 2, IIC locations. The barrier provides non-incendive outputs for
Class I, Div 2., A, B, C, D; Class II, Div. 2, F and G; Class III, Div. 2; Zone
2, IIC; and Zone 22, IIIB areas based on the entity parameter concept.
ATEX:
1 II 3G Ex nA [ic] IIC T6 Gc
1 II 3G Ex nA [ic IIIB] IIC T6 Gc
IECEx:
Ex nA [ic] IIC T6 Gc
Ex nA [ic IIIB] IIC T6 Gc

NEWSLETTER